AL13 Expansion Module
Alarm 13 is triggered if the control module has lost communication with the expansion
module for more than five minutes or communication fails within the first 15 seconds on power up.
This alarm triggers failure action C (evaporator fan only) or D (all machinery off) of Function Code Cd29 if the unit has a perishable set point.
Failure action D (all machinery off) is triggered if the unit has a frozen set point.
AL14 Phase Sequence Failure -- Electronic
Alarm 14 is triggered if the electronic phase detection system is unable to determine
the correct phase relationship.
DIRCHECK will be displayed while the relationship is determined.
If the system is unable to determine the proper relationship alarm 14 will remain active.
Additiotnal information on phase detection may be displayed at Function Code Cd41. If the right most digit of Code Cd41 is 3 or 4, this indicates incorrect motor or sensor wiring.
If the right most digit is 5, this indicates a failed current sensor assembly.
AL15 Loss Cooling Future Expansion
AL16 Compressor Current High
Alarm 16 is triggered if compressor current draw is 15% over calculated maximum 10 minutes out of the last hour.
The alarm is display only and will trigger off when the compressor operates for one hour without over current.
AL17 Phase Sequence Failure -- Pressure
Alarm 17 is triggered if a compressor start in both directions fails to generate
sufficient pressure differential.
The controller will attempt restart every twenty minutes and deactivate the alarm if successful.
This alarm triggers failure action C (evaporator fan only) or D (all machinery off) of Function Code Cd29 if the unit has a perishable set point.
Failure action D (all machinery off) is triggered if the unit has a frozen set point.
AL18 Discharge Pressure High
Alarm 18 is triggered if discharge pressure is 10% over calculated maximum for
10 minutes within the last hour.
The alarm is display only and will trigger off when the compressor operates for one hour without overpressure.
AL19 Discharge Temperature High
Alarm 19 is triggered if discharge temperature exceeds 135_C (275_F) for 10 minutes within the last hour.
The alarm is display only and will trigger off when the compressor operates for one hour without over temperature.
AL20 Control Circuit Fuse Open (24 vac)
Alarm 20 is triggered by control power fuse (F3) opening and will cause the software
shutdown of all control units.
This alarm will remain active until the fuse is replaced.
AL21 Micro Circuit Fuse Open (18 vac)
Alarm 21 is triggered by one of the fuses (F1/F2) being opened on 18 volts AC power supply to the Controller.
The suction modulation valve (SMV) will be opened and current limiting is halted. Temperature control will be maintained by cycling the compressor.
AL22 Evaporator Fan Motor Safety
Alarm 22 responds to the evaporator motor internal protectors.
The alarm is triggered by opening of either internal protector.
It will disable all control units until the motor protector resets and the unit is power cycled.
AL23 Loss of Phase B
Alarm 23 is triggered if low current draw is detected on phase B and IPCP, HPS
or IPEM is not tripped.
If the compressor should be running, the controller will initiate a start up every five minutes and trigger off if current reappears.
If the evaporator fan motors only should be running, the alarm will trigger off is current reappears.
This alarm triggers failure action C (evaporator fan only) or D (all machinery off) of Function Code Cd29 if the unit has a perishable set point.
Failure action D (all machinery off) is triggered if the unit has a frozen set point
AL24 Compressor Motor Safety
Alarm 24 is triggered when compressor is not drawing any current. It also triggers
failure action ”C” or ”D” set by function Code 29 for perishable setpoint, or ”D” for frozen setpoint.
This alarm will remain active until compressor draws current.
Table 3-6 Controller Alarm Indications (Sheet 2 of 4)
AL25 Condenser Fan Motor Safety
Alarm 25 is triggered by the opening of the condenser motor internal protector and will disable all control units except for the evaporator fans.
This alarm will remain active until the motor protector resets.
This alarm triggers failure action C (evaporator fan only) or D (all machinery off) of Function Code Cd29 if the unit has a perishable set point.
Failure action D (all machinery off) is triggered if the unit has a frozen set point
AL26 All Supply and Returntemperature Control Sensors Failure
Alarm 26 is triggered if the Controller determines that all of the control sensors
are out-of-range.
This can occur for box temperatures outside the range of --50_C to +70_C (--58_F to +158_F). This alarm triggers the failure action code set by Function Code Cd29.
AL27 A/D Accuracy Failure
The Controller has a built-in Analog to Digital (A-D) converter, used to convert
analog readings (i.e. temperature sensors, current sensors, etc.) to digital readings.
The Controller continuously performs calibration tests on the A-D converter.
If the A-D converter fails to calibrate for 30 consecutive seconds, this alarm is activated.This alarm will be inactivated as soon as the A-D converter calibrates.
AL28 Low Suction Pressure
Alarm 28 is triggered if suction pressure is below 2 psia and alarm 66 (Suction
Pressure Transducer Failure) is not active.
This alarm will be inactivated when suction pressure rises above 2 psia for three continuous minutes.
This alarm triggers failure action C (evaporator fan only) or D (all machinery off) as determined by User Selectable Failure Response if the unit has a perishable set point; Failure action D (all machinery off) if the unit has a frozen set point. Reset SMV.
AL51 Alarm List Failure
During start-up diagnostics, the EEPROM is examined to determine validity of its contents.
This is done by testing the set point and the alarm list.
If the contents are invalid, Alarm 51 is activated. During control processing, any operation involving alarm list activity that results in an error will cause Alarm 51 to be activated.
Alarm 51 is a “display only” alarm and is not written into the alarm list.
Pressing the ENTER key when “CLEAr” is displayed will result in an attempt to clear the alarm list.
If that action is successful (all alarms are inactive), Alarm 51 will be reset.
AL52 Alarm List Full
Alarm 52 is activated whenever the alarm list is determined to be full; at start-up
or after recording an alarm in the list.
Alarm 52 is displayed, but is not recorded in the alarm list. This alarm can be reset by clearing the alarm list.
This can be done only if all alarms written in the list are inactive.
AL53 Battery Pack Failure
Alarm 53 is caused by the battery pack charge being too low to provide sufficient
power for battery-backed recording. Renew replaceable batteries.
If this alarm occurs on start up, allow a unit fitted with rechargeable batteries to operate for up to 24 hours to charge rechargeable batteries sufficiently to deactivate the alarm
AL54 Primary Supply Temperature Sensor Failure (STS)
Alarm 54 is activated by an invalid primary supply temperature sensor reading that is sensed outside the range of --50 to +70_C (--58_F to +158_F) or if the probe check logic has determined there is a fault with this sensor.
If Alarm 54 is activated and the primary supply is the control sensor, the secondary supply sensor will be used for control if the unit is so equipped. If the unit does not have a secondary supply temperature sensor, and AL54 is activated, the primary return sensor reading, minus 2_C will be used for control.
NOTE
The P5 Pre-Trip test must be run to inactivate the alarm
AL55 DataCORDER Failure
This alarm activates to indicate the DataCORDER has a software failure.
To clear this alarm, reconfigure the unit to the current model number.
This failure may be the result of a voltage dip in access of 25%.
AL56 Primary Return Temperature Sensor Failure (RTS)
Alarm 56 is activated by an invalid primary return temperature sensor reading that is outside the range of --50 to +70_C (--58_F to +158_F).
If Alarm 56 is activated and the primary return is the control sensor, the secondary return sensor will be used for control if the unit is so equipped.
If the unit is not equipped with a secondary return temperature sensor or it fails, the primary supply sensor will be used for control.
NOTE
The P5 Pre-Trip test must be run to inactivate the alarm.
AL57 Ambient Temperature Sensor Failure
Alarm 57 is triggered by an ambient temperature reading outside the valid range
from --50_C (--58_F) to +70_C (+158_F).
AL58 Compressor High Pressure Safety
Alarm 58 is triggered when the compressor high discharge pressure safety switch
remains open for at least one minute.
This alarm will remain active until the pressure switch resets, at which time the compressor will restart.
AL59 Heat Termination Thermostat
Alarm 59 is triggered by the opening of the heat termination thermostat and will
result in the disabling of the heater.
This alarm will remain active until the thermostat
resets.
AL60 Defrost Temperature Sensor Failure
Alarm 60 is an indication of a probable failure of the defrost temperature sensor
(DTS).
It is triggered by the opening of the heat termination thermostat (HTT) or the failure of the DTS to go above set point within two hours of defrost initiation.
After one-half hour with a frozen range set point, or one-half hour of continuous
compressor run time, if the return air falls below 7_C (45_F), the Controller
checks to ensure the DTS reading has dropped to 10_C or below. If not, a DTS
failure alarm is given and the defrost mode is operated using the return temperature
sensor. The defrost mode will be terminated after one hour by the Controller.
AL61 Heaters Failure
Alarm 61 is triggered by detection of improper amperage resulting from heater
activation or deactivation.
Each phase of the power source is checked for proper amperage.
This alarm is a display alarm with no resulting failure action, and will
be reset by a proper amp draw of the heater.
AL62 Compressor Circuit Failure
Alarm 62 is triggered by improper current draw increase (or decrease) resulting
from compressor turn on (or off).
The compressor is expected to draw a minimum of 2 amps; failure to do so will activate the alarm.
This is a display alarm with no associated failure action and will be reset by a proper amp draw of the compressor.
AL63 Current Over Limit
Alarm 63 is triggered by the current limiting system.
If the compressor is ON and current limiting procedures cannot maintain a current level below the user selected limit, the current limit alarm is activated.
This alarm is a display alarm and is inactivated by power cycling the unit, changing the current limit via the code select Cd32, or if the current decreases below the activation level.
AL64 Discharge Temperature Over Limit
Alarm 64 is triggered if the discharge temperature sensed is outside the range of
--60_C (--76_F) to 175_C (347_F), or if the sensor is out of range.
This is a display alarm and has no associated failure action.
AL65 Discharge Pressure Transducer Failure
Alarm 65 is triggered if a compressor discharge transducer is out of range.
This is a display alarm and has no associated failure action.
AL66 Suction Pressure Transducer Failure
Alarm 66 is triggered if a suction pressure transducer is out of range.
This is a display alarm and has no associated failure action.
AL67 Humidity Sensor Failure
Alarm 67 is triggered by a humidity sensor reading outside the valid range of 0%
to 100% relative humidity.
If alarm AL67 is triggered when the dehumidification mode is activated, then the dehumidification mode will be deactivated.
AL69 Suction Temperature Sensor Failure
Alarm 69 is triggered by a suction temperature sensor reading outside the valid
range of --60_C (--76_F) to 150_C (302_F).
This is a display alarm and has no associated failure action.
NOTE
If the Controller is configured for four probes without a DataCORDER, the DataCORDER alarms AL70 and AL71 will be processed as Controller alarms AL70 and AL71.
Refer to Table 3-10.
The Controller performs self-check routines.
if an internal failure occurs, an
“ERR” alarm will appear on the display.
This is an indication the Controller
needs to be replaced.
ERROR DESCRIPTION
ERR 0 -- RAM failure Indicates that the Controller working memory has failed.
ERR Internal Microprocessor
EER 1 -- Program Memory failure Indicates a problem with the Controller program.
# Failure EER 2 -- Watchdog time--out
The Controller program has entered a mode whereby the Controller program has stopped executing.
EER 3 -- On board timer failure
The on board timers are no longer operational.
Timed items such as; defrost, etc.
may not work.
EER 4 -- Internal counter failure
Internal multi-purpose counters have failed.
These counters are used for timers and other items.
EER 5 -- A-D failure The Controller’s Analog to Digital (A-D) converter has failed.
Entr StPt Enter Setpoint (Press Arrow & Enter) The Controller is prompting the operator to enter a set point.
LO Low Main Voltage (Function Codes Cd27--38 disabled and NO alarm stored.)
This message will be alternately displayed with the set point whenever the supply
voltage is less than 75% of its proper value.
CARRIER TRANSICOLD 40X
Alarm circuit 022 break in the condenser fan.
Check or replace the brushes on the new
Code Description
A00 Green LED flashes - no alarm - unit is working properly.
A01 Exemption - pressure switch low pressure LP.
A02 Exemption - HP ciśneinia high pressure switch.
A03 Exemption - overcurrent protection of electric drive motor or overcurrent relay.
A04 Error in circuit mode, the compressor clutch ROAD.
Error A05 contactor control circuit compressor STAND BY.
A06 error in the circuit the condenser fan.
A07 Error in ventilator circuit 1st evaporator.
Error A08 ROAD heating circuit, an evaporator (optional).
A09 error in the circuits of the control valve defrosting.
A10 Error injection valve in the circuit.
A11 error in the heating circuit valve.
A12 alarm overheating the interior.
A13 alarm supercooled interior.
A14 defrost Alarm (duration> 45 min).
A15 temperature setting part from the acceptable range (-29 ° C to 30 ° C).
A16 error in the circuit water heater outlet.
A17 Overheating motosprężarki Stand by.
A18 Error Control Stand by heating an evaporator (optional).
A19 Error control valve of the liquid evaporator 1 (option).
A20 pressure switch, low pressure section, stand by (optional).
A21 break in the circuit motosprężarki stand by.
A22 break in the circuit the condenser fan.
Break in circuit A23 heating the first evaporator section of Road
A24 interval obwodziezaworu odszranianai (HGS1).
Break in circuit A25 injection valve.
A26 break in the circuit of hot gas valve (HGS2).
A27 break in the circuit heater water outlet (DWR1).
A28 Break-circuit heating stand by (EHR), an evaporator (optional).
0 komentar:
Post a Comment